Download EurotestCOMBO - Alert Electrical

Transcript
MI 3125B EurotestCOMBO
Measurements
5.8.1 Line impedance and prospective short circuit current
Circuits for measurement of line impedance
N
Ro
PE
N/L2
L/L
1
N/L2
PE/L3
PE/L3
L/L1
L1
L2
L3
N
PE
L
RE
Figure 5.32: Phase-neutral or phase-phase line impedance measurement – connection
of plug cable and 3-wire test lead
Line impedance measurement procedure
‰
‰
‰
‰
‰
‰
Select the Z-LINE sub-function.
Select test parameters (optional).
Connect test cable to the instrument.
Connect test leads to the item to be tested (see figure 5.32).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional).
Line to neutral
Line to line
Figure 5.33: Examples of line impedance measurement result
Displayed results:
Z ..............Line impedance,
ISC ............Prospective short-circuit current,
Lim ..........Low limit prospective short-circuit current value or high limit line
impedance value for the UK version.
Prospective short circuit current is calculated as follows:
ISC =
Un × kSC
Z
where:
Un ........ Nominal L-N or L1-L2 voltage (see table below),
ksc ....... Correction factor for Isc (see chapter 4.2.6).
44