Table 2. VSUP and COM Terminal Assignments
VSUP
COM
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Cascading power between two modules defeats
isolation between those modules. Cascading power from
the network module defeats all isolation between
modules in the FieldPoint bank.
Caution
Connecting Loads to the cFP-RLY-423
Connect two loads and an external power supply to one channel
of the cFP-RLY-423 as shown in Figure 2. Install a 1.5 A, 250 V
maximum, fast-acting fuse suitable for the load at the connected
IC terminal to protect the module and the load from damage.
V
C
NO
Sourcing
Load
IC
1.5 A,
250 V max
IC
NC
+
or
–
AC
Sourcing
Load
VSUP
COM
cFP-RLY-423
Figure 2. Basic Field Connection
cFP-RLY-423
4