Download VAMP 210
Transcript
2.23 Arc fault protection (50ARC/50NARC)- optional 2 Protection functions Technical description Binary input The binary input (BI) on the arc option card (see chapter 8.4) can be used to get the light indication from another relay to build selective arc protection systems. The BI signal can also be connected to any of the output relays, BO, indicators etc. offered by the output matrix (See chapter 5.4). BI is a dry input for 48 Vdc signal from binary outputs of other VAMP devices or dedicated arc protection devices by VAMP. Binary output The binary output (BO) on the arc option card (see chapters 8.4 and 8.5) can be used to give the light indication signal or any other signal or signals to another relay‘s binary input to build selective arc protection systems. Selection of the BO connected signal(s) is done with the output matrix (See chapter 5.4). BO is an internally wetted 48 Vdc signal for BI of other VAMP devices or dedicated arc protection devices by VAMP. Delayed light indication signal Relay output matrix has a delayed light indication output signal (Delayed Arc L>) available for building selective arc protection systems. Any light source combination and a delay can be configured starting from 0.01 s to 0.15 s. The resulting signal is available in the output matrix to be connected to BO, output relays etc. Pick up scaling The per unit (pu) values for pick up setting are based on the current transformer values. ArcI>: 1 pu = 1xIn = rated phase current CT value ArcI0>: 1 pu = 1xI0n = rated residual current CT value for input I01. 128 VAMP 24h support phone +358 (0)20 753 3264 VM259.EN007