Download ACC-84S - Delta Tau

Transcript
Accessory 84S
Step 4: Encoder Conversion Table Setup — for Commutation (Technique 2)
Commutation with Turbo PMAC does not require high resolution data, so in order to avoid saturations
with higher resolution BiSS encoder one must limit the commutation to 23 bits (upper). This will also
alleviate possible quantization noise effects.
This entry is preferably inserted at the end of the Encoder Conversion Table after all position/velocity
encoders in the system have been processed or have been allocated to specific entries.






Conversion Type: “Parallel position from Y word with no filtering”
Width in Bits is 23 (fixed)
Offset Location of LSB = Single Turn data stream– 23 (i.e. 26-23=3)
No shifting
Source Address (same as position ECT)
Click on “Download Entry”:
Record the location of the processed data (X:$3512 in this example). This is the commutation position
address. Equivalent Turbo PMAC Script:
I8016=$2F8800
I8017=$017003
; Unfiltered parallel pos of location Y:$78800
; Width (23 bits) and Offset (3 bits), no shifting
; Processed result at X:$3512
The commutation enable, and position address would then be:
I101=1
I183=$3512
; Mtr #1 Commutation Enable, from X Register
; Mtr #1 Commutation Position Address
Using ACC-84S with Turbo Clipper
59