Accessory 84S Step 4: Encoder Conversion Table Setup — for Commutation (Technique 2) Commutation with Turbo PMAC does not require high resolution data, so in order to avoid saturations with higher resolution BiSS encoder one must limit the commutation to 23 bits (upper). This will also alleviate possible quantization noise effects. This entry is preferably inserted at the end of the Encoder Conversion Table after all position/velocity encoders in the system have been processed or have been allocated to specific entries. Conversion Type: “Parallel position from Y word with no filtering” Width in Bits is 23 (fixed) Offset Location of LSB = Single Turn data stream– 23 (i.e. 26-23=3) No shifting Source Address (same as position ECT) Click on “Download Entry”: Record the location of the processed data (X:$3512 in this example). This is the commutation position address. Equivalent Turbo PMAC Script: I8016=$2F8800 I8017=$017003 ; Unfiltered parallel pos of location Y:$78800 ; Width (23 bits) and Offset (3 bits), no shifting ; Processed result at X:$3512 The commutation enable, and position address would then be: I101=1 I183=$3512 ; Mtr #1 Commutation Enable, from X Register ; Mtr #1 Commutation Position Address Using ACC-84S with Turbo Clipper 59