Download EN / ACSM1 Speed and Torque Control Program

Transcript
310
TOF
(10058)
Illustration
TOF
86
TLA1 1 msec
(1)
IN
ET(86)
ET
PT
Q(86)
Q
Execution time
1.10 µs
Operation
The output (Q) is set to 1, when the input (IN) is set to 1. The output is reset to zero
when the input has been 0 for a time defined by the pulse time input (PT).
Elapsed time count (ET) starts when the input is set to 0 and stops when the input is set
to 1.
Example:
IN
ET
Q
ET
ET
PT
Inputs
PT
Input (IN): Boolean
Pulse time input (PT): DINT (1 = 1 µs)
Outputs
Elapsed time output (ET): DINT (1 = 1 µs)
Output (Q): Boolean
TON
(10059)
Illustration
TON
87
TLA1 1 msec
(1)
IN
ET
PT
Q
Execution time
Standard function blocks
1.22 µs
ET(87)
Q(87)