Download RemoteTRAK

Transcript
RM-8INS-U
Overview
Instrumentation Analog Input Module
Eight isolated input channels provide 16 bit high resolution analog measurements. More
information can be found in the on-line help supplied with the SIXNET I/O Tool Kit.
Number of Channels
8 (16 bit resolution)
Input Ranges
JKERTBCNS Thermocouples, 62 mV to 10V, 4 - 20 mA
Input Impedance (4-20 mA)
100 ohms Note: input voltage drop = 2 volts at 20 mA
Input Impedance (other ranges) 200K Ohms
-U Wiring
Two input terminals are provided for each measurement channel. Channel to channel isolation
is provided.
Current
Shunts
Precision 100 ohm current shunts, beneath the hinged access door in the wiring base, pass
current and maintain loop integrity even if the module is unplugged. A spare shunt is provided
and may be simply inserted in place of any socketed shunt that open circuits as a result of a
current overload.
I/O Registers
Function
Analog Inputs
Section 6
SIXNET Registers
AX0 – AX7
Analog Input Modules
Modbus Registers
30001 – 30008 Bipolar values: -32768
15