5 Practicability of installation
The system should be installed only by specialised contractors who have successfully undergone training and
registration by the Certificate holder.
Note: The BBA operates a UKAS-accredited Approved Installer Scheme for external wall insulation; details of
approved installer companies are included on the BBA’s website (www.bbacerts.co.uk).
6 Thermal performance
6.1 Calculations of thermal transmittance (U value) should be carried out in accordance with BS EN ISO 6946 : 2007
and BRE Report BR 443 : 2006, using the insulation manufacturer’s declared thermal conductivity (␭D value) of
0.032 W·m–1·K–1.
6.2 The U value of a competed wall will depend on the selected insulation thickness and fixing method, the
insulation value of the substrate masonry and its internal finish. Figures for typical design U values, calculated in
accordance with section 6.1, are given in Table 2.
Table 2 Insulation thickness required to achieve some typical design values (1)(2)
U-value
(W·m–2·K–1)
Insulation thickness requirement (mm)(3)
215 mm Brickwork,
␭ = 0.56 W·m–1·K–1
200 mm Dense blockwork,
␭ = 1.75 W·m–1·K–1
0.19
170
180
0.26
120
130
0.28
110
120
0.30
100
110
0.35
90
100
(1) The following values for other elements of the construction were used:
• external boundary resistance (Rse) — 0.04 m2·K·W–1
• render (14 mm sand and cement) — ␭ = 1.0 W·m–1·K–1, µ = 6 (wet)
• EPS 70E (215 mm) — 93.3%
• 215 mm brickwork (protected) — ␭ = 0.56 W·m–1·K–1 (µ = 10) [or 200 mm blockwork, ␭ = 1.75 W·m–1·K–1
(µ = 100 and 6.7%)]
• mortar — ␭ = 0.88 W·m–1·K–1
• plaster (13 mm) —␭ = 0.57 W·m–1·K–1, µ = 10
• internal boundary resistance (Rsi) — 0.13 m2·K·W–1.
(2) Fixing regime 6.944 fixings per m2 (5 fixings per board) with a point thermal transmittance, ␹ = 0.003W·K–1.
(3) Based upon incremental insulation thickness of 10 mm.
6.3 The system can contribute to maintaining continuity of thermal insulation at junctions between elements and
openings. For Accredited Construction Details, the corresponding ␺-values (psi) in BRE Information Paper IP 1/06,
Table 3, may be used in carbon emission calculations in Scotland and Northern Ireland. Detailed guidance for
other junctions and on limiting heat loss by air infiltration can be found in:
England and Wales — Approved Documents to Part L and, for new thermal elements to existing buildings, Accredited
Construction Details (version 1.0). For new-build, also see SAP 2009, Appendix K, and the iSBEM User Manual
Scotland — Accredited Construction Details (Scotland)
Northern Ireland — Accredited Construction Details (version 1.0).
Page 6 of 17