Deadband
The Windows DDE interface to InTouch can get temporarily overloaded if a lot of channels
all change at once. Unless great care is taken in installation the 16 bit analog inputs are bound
to have some noise and flutter on them. This can unnecessarily overload the system,
particularly if they are measuring slow changing parameters such as temperatures or magnet
currents. For these channels, and in general unless the full speed accuracy is required, use the
filtering within the DI, and use the deadband system within InTouch.
Set the deadband to a reasonable figure unless very high accuracy is required. A deadband
value of 100 on a C board input still allows readings accurate to 0.2%, and most process
variables are not measured to that accuracy.
Do not check the "use tagname as Item Name" box.
Click on Save, then Done when all tags are completed.