Download L-Series Integrated Speed Control
Transcript
L-Series Integrated Speed Control Manual 26250 Overview Tab The overview tab provides speed sensing and position control configuration settings. Figure 6-2. Configuration Editor—OVERVIEW TAB Speed Input Configuration Settings These settings are used to determine the conversion from speed input pulses to engine rpm, as well as engine torsional filtering. Based on the security settings, the speed input configuration settings (with the exception of the sensor type) can also be modified from the Edit Speed Settings selection under the Tools menu (refer to Chapter 7, Editing of Speed Settings). Sensor Type Set to either MPU or Ignition. This function requires engine speed pulses present on either the ignition pin input (pin 12) or the MPU pin input (pin 11). Engine Type Set to either 2-stroke or 4-stroke. Number of Cylinders Sets the number of cylinders. From the sample table below, select the value that corresponds to the number of crankshaft degrees between ignition pulses. Allowed values: 1—20 68 Woodward