Download MLC-9000 User Manual - Instrumentation Central

Transcript
MLC 9000 User Guide
4.3.5
Setpoint Ramp Rate
This parameter defines the setpoint ramp rate in units/hour.
Adjustment Range:
0001 (1 dec.) to 270Fh (9999 dec.) and 0000 (OFF).
Default Value:
0000 (OFF).
Automatic Change:
None.
Effects of Change on
Other Parameters:
If this parameter value is changed, the Actual Setpoint
value (see Subsection 4.3.4) is modified according to
the Actual Setpoint calculation.
4.4
CONTROL PARAMETERS (LCM Class 3)
4.4.1
Manual Control Enable/Disable
This parameter selects/de-selects Manual Control (see also Appendix C).
Adjustment Range:
1 (Manual Control ON) or 0 (Manual Control OFF).
Default Value:
0 (Manual Control OFF).
Automatic Change:
None.
Effects of Changes on
Other Parameters:
When Manual Control Mode is selected, an active
Loop Alarm is turned off and Loop Alarm is disabled
(see Subsection 4.4.13) whilst Manual Control Mode is
used. Upon exit from Manual Control Mode, the Loop
Alarm is automatically re-enabled and its original state
is restored.
4.4.2
Manual Power
This parameter sets the percentage of output power when manual control is selected
(see also Appendix C). This parameter is not applicable if Manual Control is not
selected.
Adjustment Range:
0000 (0%) to 0064h (100%) (HEAT output only
configured) or FF9Ch (−100%) to 0064h (+100%)
(HEAT and COOL outputs configured).
Default Value:
0000 (0%).
Automatic Change:
Forced within range, if necessary, when Control Type
(see Subsection 4.4.14) is changed.
Effect of Changes on
Other Parameters:
None.
4-11