Model 6 OMNI-Center Enhanced Section 5—Operation Bulletin No. 80445-109-01A January 2001 Table 15: Read/Write Registers RAM Address Relative Address Code Description Range Default MOTOR LOGIC PLUS Command Register (C6 hex) 01H C6 1B3 COM-LINE 02H Stop 03H Display lock 04H Display unlock 05H Network program enable 06H Network program disable C8 1B4 Scale 0, 1, 1–2; 16POWERLOGIC bit signed scale word (2’s parameter complement, read only) CA 1B5 LV Low voltage threshold 170 V (450 V ) - HV setting 435 CC 1B6 HV High voltage threshold LV setting 528 V (660 V ) 500 CE 1B7 VUB Voltage unbalance threshold 2–15% or 999% 5% D0 1B8 MULT CT/turns effective ratio 1 or 10–200 1 D2 1B9 OC Overcurrent threshold OL current range Min. rating D4 1BA UC Undercurrent threshold 0.5 x OC Min. to OC Max., Off 0.8 x OC Min. D6 1BB CUB Current unbalance threshold 2–25% or 999% 6% D8 1BC TC Overcurrent trip class « « 5, J5, 10, J10, 15, J15, 20, J20, 30, J30 (J = Jam protection is enabled) Model dependent 5 5 decimal J5 133 decimal 10 10 decimal J10 138 decimal 15 15 decimal J15 143 decimal 20 20 decimal J20 148 decimal 30 30 decimal J30 158 decimal DA 1BD RD1 Rapid cycle timer 2–500 seconds 10 DC 1BE RD2 Restart delay all faults except undercurrent 2–500 minutes 8 « Can only be viewed via network 56 « Command Line Reset/run/ stop, display lock, network configuration enable Start/reset © 2001 Schneider Electric All Rights Reserved