Integer
Ibase value, increment, action, start output, stop output
I is the flag for an Integer I/O point type
base value – value at which the Point Manager will trigger the first event.
This value is a 32-bit integer value. Do not use the scaled value but the
raw integer or count.
increment – the increment value at the Point Manager that will trigger
additional events. This value is a 32-bit integer value.
action - ‘N’ - do nothing, ‘E’ – email, ‘L’ – log event in the Event Log, ‘M’
– log and email, ‘A’ – alarm and log the event, and ‘B’ – alarm, log and
email.
start output – when an event occurs, the Point Manager will generate a
output start operation for the specified row. (See the “KS” command).
If this number is greater than 32768 (8th bit set) then this parameter
refers to a set of outputs where 32768 is output set 0 and 32769 is set 1
and 327611 is set 3. 0 is no action.
stop output – when an event occurs, the Point Manager will generate a
output stop operation for the specified row. (See the “KS” command).
If this number is greater than 32768 (8th bit set) then this parameter
refers to a set of outputs where 32768 is output set 0 and 32769 is set 1
and 327611 is set 3. 0 is no action.
Data
Dchange action, change start output, change stop output
change action – trigger an event when the data changes. The following are
the possible actions: ‘N’ - do nothing, ‘E’ – email, ‘L’ – log event in
the Event Log, ‘M’ – log and email, ‘A’ – alarm and log the event, and
‘B’ – alarm, log and email.
Change start output – when an event occurs, the Point Manager will
generate a output start operation for the specified row. (See the “KS”
command). If this number is greater than 32768 (8th bit set) then this
parameter refers to a set of outputs where 32768 is output set 0 and
32769 is set 1 and 327611 is set 3. 0 is no action.
change stop output – when an event occurs, the Point Manager will generate
a output stop operation for the specified row. (See the “KS”
command). If this number is greater than 32768 (8th bit set) then this
parameter refers to a set of outputs where 32768 is output set 0 and
32769 is set 1 and 327611 is set 3. 0 is no action.
State
Sto 1 action, from 1 action, 1 state,…, to x action, from x action, x state[,to 1 start
output, to 1 stop output, from 1 start output, from 1 stop output,…, to x start output,
to x stop output, from x start output, from x stop output]
S is the flag for a State I/O point type.
84 • Commands
Point Manager Manual