Choice of protective
devices
Circuit breakers – Fuses
Step protection by means of fuses
Type Gg HBC fuses must be used with the following ratings:
b classic and comfort ranges: 1.6 In
b harmony range: 1.5 In.
DB109710
Note: when 2 steps are protected by the same set of fuses, the coefficients are:
b 1.4 In for classic and harmony steps
b 1.6 In for comfort steps.
Protection of the transformer
supplying the auxiliaries
Use of a transformer to supply the auxiliaries
The transformer must be sufficiently powerful to supply the contactor coils
(drive and holding), the controllers and other energy-consuming devices
(fans, lamps, etc.).
Table showing the choice of protective devices at the
transformer primary for transformers with an inrush current of
25 In (primary voltage 400 V)
Power
VA
63
100
160
250
400
630
800
1000
Primary In
A
aM fuse
A
Circuit breaker
Curve B
0.16
0.25
0.4
0.62
1
1.57
2
2.5
1
1
1
2
4
4
4
6
1
1
1
2
2
3
4
6
Table showing the choice of protective devices at the
transformer secondary (secondary voltage 230 V single-phase)
Power
VA
Secondary In
A
63
0.27
100
0.43
160
0.70
250
1.09
400
1.74
630
2.74
800
3.49
1000
4.35
(1) No overload protection provided.
28 avril 2006
gG fuse
A
Circuit breaker
Curve C
0.5 (1)
0.5
1
1
2
4
4
4
0.5 (1)
0.5
0.75
1
2
3
4
4
7
27