E–4 Block Transfer Write and Block Transfer Read Configurations for 2 Output/6 Input 1771-N Series Modules Decimal Bit (Octal Bit) Definition Bit 15 (17) CJ alarm enable. A value of 1 enables over and underrange indication for the cold junction channel. If the module does not have a cold junction channel, this bit is 0. Word 4 Bits 00–15 (00–17) Real time sample. Sample time in milliseconds. 0 = off. RTS minimum is 100msec (counts = 100). Maximum 10 seconds in binary; 9.999 seconds in BCD. Word 5 Bits 00–15 (00–17) Low scale value for channel 1. Scale values are limited to +32767 in binary format; +7999 in BCD format. Word 6 Bits 00–15 (00–17) High scale value for channel 1. Scale values are limited to +32767 in binary format; +7999 in BCD format. Word 7 Bits 00–15 (00–17) Low clamp value for channel 1. The channel output will not be allowed to go below this value (in scaled units) regardless of the data sent to the module. Clamp values are limited to +32767 in binary format; +7999 in BCD format. Word 8 Bits 00–15 (00–17) High clamp value for channel 1. The channel output will not be allowed to go above this value (in scaled units) regardless of the data sent to the module. Clamp values are limited to +32767 in binary format; +7999 in BCD format. Bits 00–11 (00–13) Maximum ramp rate. If this field is not 0, the module will limit the maximum rate of change for this channel to be a percentage of the scaled range of the module. Legal values are from 1 to 200%. Bit 12 (14) Constant = 0 Bits 13–14 (15–16) Reset state. This field controls what the channel will output if the I/O reset line is asserted: 00 binary = last state; 01 binary = minimum output; (example: < –10V, < 4mA) 10 binary = maximum output; (example: > 10V, > 22mA) 11 binary = user reset value. Bit 15 (17) Alarm enable. If set to 1, the module reports high clamp, low clamp and rate limit. If 0, these warnings are suppressed. Bits 00–15 (00–17) Reset value. If the user selects the channel to go to a user reset value upon I/O reset, the value in scaled units is entered here. Otherwise, set to 0. Word Word 9 Word 10 Word 11 thru 16 Publication 1771-6.5.127 – June 1999 Same as words 5 thru 10 but for channel 2. Word 17 Bits 00–15 (00–17) Low scale value for channel 3. Word 18 Bits 00–15 (00–17) High scale value for channel 3. Word 19 Bits 00–15 (00–17) Low alarm value for channel 3. Word 20 Bits 00–15 (00–17) High alarm value for channel 3. Word 21 Bits 00–14 (00–16) Rate alarm. If the channel’s input changes at a rate faster than this value and the alarm enable bit is set, the channel will indicate a rate alarm condition. Legal values are from 0.05 to 50% of full scale per second.