3.2.8.1 Recommendations for Analogue Signals Wiring a) If the analogue signal source is single-ended, use a 2-wire shielded cable as follows: 1st wire connects the live signal to the drive positive input (+); 2nd wire connects the signal ground to the drive negative input(-). b) If the analogue signal source is differential and the signal source ground is isolated from the drive GND, use a 3-wire shielded cable as follows: 1st wire connects the signal plus to the drive positive input (+); 2nd wire connects the signal minus to the drive negative input (-) and 3rd wire connects the source ground to the drive GND c) If the analogue signal source is differential and the signal source ground is common with the drive GND, use a 2-wire shielded cable as follows: 1st wire connects the signal plus to the drive positive input (+); 2nd wire connects the signal minus to the drive negative input (-) d) For all of the above cases, connect the cable shield to the drive I/O connector frame and leave the other shield end unconnected to the signal source. To further increase the noise protection, use a double shielded cable with inner shield connected to drive GND and outer shield connected to the drive I/O connector frame. Leave both shields unconnected on the signal source side e) If the signal source output voltage is larger than +/-10V, use a 3-resistor differential divider, located near the IDM680 I/O connector. Choose the divider resistances as low as possible, close to the signal source output current limit, to minimize the noise Figure 3.31 J9 – 24 V Pulse & Direction connection © Technosoft 2008 56 IDM680 Technical Reference