Download IDM680 Intelligent Drive - User Manual

Transcript
3.2.8.1
Recommendations for Analogue Signals Wiring
a) If the analogue signal source is single-ended, use a 2-wire shielded cable as follows: 1st wire
connects the live signal to the drive positive input (+); 2nd wire connects the signal ground to
the drive negative input(-).
b) If the analogue signal source is differential and the signal source ground is isolated from the
drive GND, use a 3-wire shielded cable as follows: 1st wire connects the signal plus to the
drive positive input (+); 2nd wire connects the signal minus to the drive negative input (-) and
3rd wire connects the source ground to the drive GND
c) If the analogue signal source is differential and the signal source ground is common with the
drive GND, use a 2-wire shielded cable as follows: 1st wire connects the signal plus to the
drive positive input (+); 2nd wire connects the signal minus to the drive negative input (-)
d) For all of the above cases, connect the cable shield to the drive I/O connector frame and
leave the other shield end unconnected to the signal source. To further increase the noise
protection, use a double shielded cable with inner shield connected to drive GND and outer
shield connected to the drive I/O connector frame. Leave both shields unconnected on the
signal source side
e) If the signal source output voltage is larger than +/-10V, use a 3-resistor differential divider,
located near the IDM680 I/O connector. Choose the divider resistances as low as possible,
close to the signal source output current limit, to minimize the noise
Figure 3.31 J9 – 24 V Pulse & Direction connection
© Technosoft 2008
56
IDM680 Technical Reference