Next Generation Guardmaster Safety Relay (GSR)
Speed Status Only
Circuit Components
• Bulletin 872C proximity sensors
• GLP safety relay
Circuit Status
The GLP safety relay has a Logic setting of 8: (speed status only), a Safe Limited Speed (SLS1) setting of 0 (0.5 Hz,
10.1 seconds) and a maximum (SLS2/Time) speed setting of 5 (200 Hz).
TIP
Start the GLP configuration from “9” to configure for speed status only.
Operating Principle
The GLP safety relay is used to provide outputs that are a function of the speed the proximity sensors detect and the
thresholds set by the SLS1 and SLS2/Time switches.
When the proximity sensors detect speed below the SLS1 setting, all GLP outputs are OFF.
When the proximity sensors detect speed above the SLS1 setting and below the SLS2/Time setting, the 51 and L61
outputs turn ON.
When the proximity sensors detect speed above the SLS2 setting, the L11, X14, X24, and Y32 outputs turn ON. The 51
and L61 outputs remain ON.
When the proximity sensors detect speed below the SLS2 setting, the L11, X14, X24, and Y32 outputs turn OFF
immediately. The 51 and L61 outputs remain ON.
When the proximity sensors detect speed below the SLS1 (0.5 Hz) setting, the GLP safety relay starts the SLS1 timer. After
10.1 seconds, the GLP safety relay turns off 51 and L61.
Fault Detection
Upon power-up, the GLP safety relay performs internal checks. If the checks are completed safely, the GLP safety relay
reads the speed of the redundant proximity sensors, and turns ON the appropriate outputs. The 51/L61, X14/X24, and
L11 outputs are safety rated outputs that check for short circuit conditions.
Ratings
The safety function meets the safety performance requirements of SIL CL2 per IEC 62061:2005 and has a Category 3
structure that can be used in systems that require Performance Levels up to PLd per ISO13849-1:2006.