Chapter 2 Installation 7 2.4 Installation Procedures Note Before commencing installation hot works, release all nitrogen holding charges from the indoor and outdoor units. Installing pipelines Note 1. Protect copper pipes from heat sources. Isolate copper pipes from structures or other obstacles using rigid supports. Avoid dust, water vapor and irrelevant objects from entering copper pipes. 2. Use a good quality, silver-based solder for all brazed connections. Use refrigeration grade copper pipes and fittings throughout the installation. Purge all pipes with nitrogen during brazing to prevent oxidation. 1. Identify the pipe sizes Refer to 2.6 Installing Unit Pipes in Liebert.PEX Series Air Conditioner User Manual for pipe sizes. 2. Identify the condenser installation height Refer to 2.6 Installing Unit Pipes in Liebert.PEX Series Air Conditioner User Manual for installation height. 3. Install the pipes Install the pipes according to local and national codes and standards. Connecting external power (external power supply of the condenser) 1. Identify the cable specifications Select the power supply cables and start/stop signal cables of the condenser according to site conditions, such as the distance between the indoor unit and the condenser. Table 2-1 Operation current of fan under 400V voltage Condenser Model LSF12 LSF18 LSF24 LSF32 LSF38, LSF42, LSF52, LDF42, LDF52 LSF62, LSF72, LDF62, LDF72 LSF76, LSF85, LDF76, LDF85 FLA (A) 0.79 1.45 1.65 1.05 2.4 3.3 4.8 Note 1. It is recommended to use the 20AWG (0.52mm2) cable as the condenser start/stop signal cable. 2. The outdoor air cooled condenser requires a three-phase, neutral and earth power supply. The indoor PEX unit is the recommended point of connection for this electrical service and includes a three-pole circuit breaker rated at 16 amps. 3. The cables should not contact hot objects, such as the copper pipe and water pipe without insulation, to avoid damaging the insulation layers. 4. The cables should be connected in accordance with the local regulations. 2. Connect the cables See Figure 2-5, Figure 2-6 and Appendix 1 Circuit Diagram for the connections of external power cables. Liebert.PEX Condenser User Manual