PTQ-PDPS ♦ Quantum / Unity Platform
PROFIBUS DP Slave Module
Modifying the Configuration File
Parameter Data Structure
SPC3 evaluates the first seven data bytes (without user prm data), or the first
eight data bytes (with user prm data). The first seven bytes are specified
according to the standard. The eighth byte is used for SPC3-specific
communications. The additional bytes are available to the application.
Byte
0
Bit Position
Designation
7
6
5
4
3
2
1
0
Lock
Reg
Unio
Req
Sync
Req
Free
Req
WD on
Res
Res
Res
Station status
1
WD_Fact_1
2
WD_Fact_2
3
MinTSDR
4
Ident_Number_High
5
Ident_Number_Low
6
Group_Ident
7
Spec_User_Prm_Byte
8 to 243
User_Prm_Data
Byte 7
Spec_User_Prm_Byte
Bit
Name
Significance
Default State
0
Dis_Startbit
The start bit monitoring in the receiver
is switched off with this bit
Dis_Startbit = 1,
Stop bit monitoring in the receiver is
switched off with this bit
Dis_Stopbit = 0
1
Page 52 of 92
Dis_Stopbit
That is, start bit monitoring is switched off.
That is, stop bit monitoring is not switched
off.