Download MPPT 80-600 User Manual
Transcript
Operation Table 3-6 Warning messages Display Text (Description) Warning ID Definition OutputUVWrn W12 24 V System: Output voltage has fallen below 20.0 VDC for 10 seconds. The warning clears itself when the voltage rises above 21.0 VDC for 10 seconds. (Output under voltage warning) 48 V System: Output voltage has fallen below 40.0 VDC for 10 seconds. The warning clears itself when the voltage rises above 42.0 VDC for 10 seconds. OutputOVWrn W34 24 V System: Output voltage has risen above 31.5 VDC for 10 seconds. The warning clears itself when the voltage falls below 30.5 VDC for 10 seconds. (Output over voltage warning) 48 V System: Output voltage has risen above 63.0 VDC for 10 seconds. The warning clears itself when the voltage falls below 61.0 VDC for 10 seconds. HsOTWrn W35 Heat sink temperature has risen above 85 °C (185 °F) for 10 seconds. The warning clears itself when the heat sink temperature falls below 80 °C (176 °F) for 10 seconds. (Heat sink over temperature warning) 620 610 600 590 580 570 PV Input Voltage 560 (Volts) 550 Vpv Error Level Vpv Clear Level 540 530 520 510 500 -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 Heat Sink Temperature (Celsius) Figure 3-2 Over voltage protection 3–10 975-0560-01-01 Revision B