Download MPPT 80-600 User Manual

Transcript
Operation
Table 3-6 Warning messages
Display Text
(Description)
Warning ID
Definition
OutputUVWrn
W12
24 V System: Output voltage has fallen below 20.0 VDC for
10 seconds. The warning clears itself when the voltage rises
above 21.0 VDC for 10 seconds.
(Output under
voltage warning)
48 V System: Output voltage has fallen below 40.0 VDC for
10 seconds. The warning clears itself when the voltage rises
above 42.0 VDC for 10 seconds.
OutputOVWrn
W34
24 V System: Output voltage has risen above 31.5 VDC for
10 seconds. The warning clears itself when the voltage falls below
30.5 VDC for 10 seconds.
(Output over
voltage warning)
48 V System: Output voltage has risen above 63.0 VDC for
10 seconds. The warning clears itself when the voltage falls below
61.0 VDC for 10 seconds.
HsOTWrn
W35
Heat sink temperature has risen above 85 °C (185 °F) for
10 seconds. The warning clears itself when the heat sink
temperature falls below 80 °C (176 °F) for 10 seconds.
(Heat sink over
temperature
warning)
620
610
600
590
580
570
PV Input
Voltage 560
(Volts) 550
Vpv Error Level
Vpv Clear Level
540
530
520
510
500
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
Heat Sink Temperature (Celsius)
Figure 3-2 Over voltage protection
3–10
975-0560-01-01 Revision B