Download UV tech HD700 Advanced User Manual

Transcript
2 Parameter detailed description
P01.29
Output frequency detection (FDT) width
Coding
RW
US
■
■
Range
0.00Hz~P01.28
Default
0.00Hz
Change mode
P01.30
PT
ND
PS
PT
ND
PS
■
■
Run&Stop
Output frequency detection (FDT) indicator
RW
US
Coding
Range
0: off
1: on
Change mode
Actual
If the absolute value of P05.11 (output frequency) is more than or equal to the value of P01.28 adding P01.29, output
frequency detection signal is valid. If the absolute value of P05.11 (output frequency) is less than or equal to the value of
P01.28 subtracting P01.29, output frequency detection signal is invalid. As shown in the figure:
F
(Output Freqency)
P01.29
P01.28
P01.29
T
P01.30
Figure 2-1-3
FDT
...UVtech HD700 Advance User Manual...
Page 17 of 225