Download MemoryPAT User Manual

Transcript
FIRST STOP SAFETY
30
SPECIFICATION
EARTH CONTINUITY TEST
CURRENT
OC VOLTAGE
TOLERANCE
FAIL THRESHOLD
1m
5m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
150 mA
8 - 10 V
5% + 20 mΩ
(based on user selected lead length as below)
>0.1 ohms
>0.2 ohms
>0.3 ohms
>0.4 ohms
>0.5 ohms
>0.6 ohms
>0.7 ohms
>0.8 ohms
>0.9 ohms
>1.0 ohms
>1.1 ohms
Default
INSULATION TEST
TEST VOLTAGE
500V
TEST VOLTAGE
250V
MEASUREMENT TOLERANCE
FAIL THRESHOLD CLASS I
FAIL THRESHOLD CLASS II
+/- 10% into 0.5 Mohm
+/- 10% into 0.5 Mohm
5% + 0.1
< 1 MΩ
< 2 MΩ
POLARITY TEST
TEST VOLTAGE
TESTS
30 V DC
Live open
Neutral open
Live to Neutral short
POWER ON TEST
TEST VOLTAGE
RESISTANCE
MemoryPAT
40 V rms
ON if <10 kohm
Issue 2.1