INPUT MODULE (1- IN) (Cont’d) Input Sensor Correction Constants (SPAN & SHFt) If the controller temperature disagrees with a reference temperature instrument or if the temperature sensor has a known calibration, the controller temperature can be compensated by a correction slope (SPAN) and offset (SHFt). SPAN - 0.001 to 9.999 SHFt - -999 to 9999 The following equation expresses the relationship: Desired Display Temp = (Controller Temp x SPAN) + SHFt EX1.) The controller reads 293°F while a reference instrument indicates 300°F. A SHFT value of +7°F corrects the controller indication to match the reference. (Use SPAN = 1.000) EX2.) A thermocouple probe is calibrated over the region of operation to achieve more accurate temperature control. The calibration results are as follows: Desired Temperature Thermocouple Output 400.0F 395.0F 800.0F 804.0F SPAN = 800F - 400F = 0.978 804F - 395F SHFT = 400F - (0.978 x 395F) = 13.7°F Auto Setpoint Ramp Rate (SPrP) The setpoint can be programmed to ramp independent of the controller’s display resolution. The setpoint ramp rate can reduce thermal shock to the process, reduce temperature overshoot on start-up or setpoint changes, or ramp the process at a controlled rate SPrP - 0.1 to 999.9 degrees/minute A ramp value of zero disables setpoint ramping. If the user input is programmed for setpoint ramp, it affects the enabling and disabling of setpoint ramping (refer to user input section). Setpoint ramping is initiated on power-up or when the setpoint value is changed and is indicated by a decimal point flashing in the far right corner of the main display. Note: The auto setpoint ramp rate is independent from the operation of a profile. Once the ramping setpoint reaches the target setpoint, the setpoint ramp rate is disengaged until the setpoint is changed again. If the ramp value is changed during ramping, the new ramp rate takes effect. If the setpoint is ramping prior to invoking Auto-Tune, the ramping is suspended during auto-tune and then resumed afterward using the current temperature as a starting value. Deviation and band alarms are relative to the target setpoint, not the ramping setpoint. If the analog output is programmed to transmit the setpoint value, the instantaneous ramping setpoint value is transmitted. SPAN value of 0.978 and SHFT value of 13.7°F corrects the indicator to the probe. Setpoint Limit Values (SPLO & SPHI) The controller has programmable high and low setpoint limit values to restrict the setting range of the setpoint. Set the limit values so that the temperature setpoint value cannot be set outside the safe operating area of the process. SPLO - -999 to 9999 SPHI - -999 to 9999 Note: Depending on the ramp rate relative to the process dynamics, the actual process temperature may not track the ramping setpoint value. -30-