Installation and Wiring 2-15 4. At the other end of the cable, cut the drain wire and foil shield back to the cable and apply shrink wrap. 5. Connect the signal wires to the terminal block. Connect the other end of the cable to the analog input device. 6. Repeat steps 1 through 5 for each channel on the module. TIP See Appendix D Using Thermocouple Junctions for additional information on wiring grounded, ungrounded, and exposed thermocouple types. Wiring the Terminal Blocks The following figures show how to wire the terminal blocks. Figure 2.1 1790D-4R0-RTD Input Module D-Shell Wiring NC +24V NC CH2_B CH3-B NC NC CH0_B CH1_B NC +24V +24V CH2_A CH3_A NC NC CH0_A CH1_A NC 19 18 37 17 36 16 35 15 34 13 14 33 31 32 11 12 30 9 10 29 28 8 27 7 26 5 6 25 24 3 4 23 22 1 2 21 20 GND NC NC NC NC GND NC NC NC GND NC NC NC NC NC NC NC NC 43256 Wire pins 17, 18, 19 to Field Power (+) 24V dc Wire pins 35, 36, 37 to Field Power (-) GND Figure 2.2 1790D-T4R0 and 179P-T4R0 RTD Input Module D-Shell Wiring +24V CH1_A CH2_A NC NC CH0_A NC NC CH3_A NC 1 3 2 5 4 7 6 11 9 8 10 12 17 15 13 14 16 19 18 20 GND CH1_B CH2_B NC NC CH0-B NC NC CH3_B NC 432X1 Wire pin 1 to Field Power (+) 24V dc Wire pin 2 to Field Power (-) GND IMPORTANT When using an ungrounded thermocouple, the shield must be connected to ground at the module end. Publication 1790-UM003A-EN-P - May 2002