Download INGEPAC PL70FV User Manual
Transcript
23BPROTECTION FUNCTIONS DESCRIPTION AND SETTINGS 2. “Voltage presence” ON: Voltage presence. The following priority levels have been established to determine voltage presence. 1. “Relay CAPDIS 1” and “Relay CAPDIS 2” digital inputs. 2. “Voltage presence” digital input. 3. Conventional voltage capacitive splitter input. Measurement corrections This function only applies to models with voltage measurement with an input for a capacitive splitter (PL70SC and RS bushing insulator). Each measurement has a correction factor, which multiplies the measurement in order to correct any differences between the different sensors and, in the case of voltage, the bushing insulators and signalling circuits. In the case of RS, there are three voltage factors, one for each phase. Setting Voltage factor Phase A voltage factor Phase B voltage factor Phase C voltage factor Minimum 0,2000 0,2000 0,2000 0,2000 Maximum 1,8000 1,8000 1,8000 1,8000 Step 0,0001 0,0001 0,0001 0,0001 Remarks SC family (Models B and D) RS family RS family RS family The unit is equipped with a further Setting: Bushing insulator capacity, which must be set in accordance with the capacity of the bushing insulator to which it is to be connected. If an incorrect setting is employed, the voltage measurement will be affected. Setting Minimum Maximum Step Bushing insulator capacity (pF) 3,0 35,0 Remarks 0,1 In the event of the bushing insulator’s capacity not being known, the defect value 20 pF should be employed. In a given installation in which a 20 pF setting measures V (kV), a change in the setting to C pF will result in the measurement being multiplied by 20/C, that is to say, if the setting is programmed at 10 pF, the measurement will be doubled. A more precise measurement is obtained with the correction factor. If, for example, the measurement is 24 kV when it should be 22, a voltage factor of 22/22 = 0.92 should be programmed. The same is applicable to currents: if a measurement of 580 A instead of 600 A is obtained in phase C, the “phase C factor” should be set at 600/580 = 1.03 A specific setting indicates if xenon lights have been connected. When lights are connected, the measurements are corrected. Setting Minimum Maximum Step Light correction Remarks XENON/N O In PL70RS units with voltage measurement and capacitive splitter input, voltage is calculated using the current circulating through a capacitive circuit. Due to the characteristics of the capacitive circuits, a phase difference is entered between the current circulating through the circuit and the voltage to be measured. This phase difference is compensated with the “lead/lag adjustment” setting. Setting Minimum Maximum Step Remarks Angle correction (deg.) 0,0 359,9 0,1 These settings can be found in the “Programmable factors and bushing insulators” screen in the Console. Ingeteam Technology S.A. PL70 User Manual 90