Document: LT0115 IO-NET Programmable Controller User’s Manual
System Description
1.1.1
NON-PROGRAMMED MODE
4444444444444444444
In non-programmed mode each of the 32 outputs on the controller will
mimic the state of 32 inputs on a different controller - its "pair".
The controller does not have to be programmed with a specific control
program. Non-programmed mode is described in more detail in Chapter 6.
The controller cannot transmit or receive zone data in non programmed
mode.
1.1.2
PROGRAMMED MODE
444444444444444
In programmed mode a specific control program is field programmed into
the controller and the state of the outputs on the controller is
determined by logic expressions defined in the control program. The
control program also includes the definition of network parameters which
allow setting of values such as RTS (Request to Send) delays, etc. The
control program also specifies whether the controller has an RZDU data
input connected and whether it is to transmit that data onto the IO-NET
network or not.
In programmed mode the state of each output is set according to a logic
expression which may include the state of:
1.
2.
3.
4.
5.
6.
7.
8.
one of its own inputs
an input on any other controller on the network
one of its own outputs
any zone on one or more F4000/F3200 fire panels connected to the
network.
one of its own logic variables
some system conditions such as network fault.
the state of a timer
the "scan status" of any IO-NET controller or F4000/F3200 fire
panel.
In programmed mode a control program is generated from a user source
file and is programmed into the controller EPROM. A controller EPROM
can be re-programmed a limited number of times, typically 8 to 12,
depending on the size of the control program.
Examples of possible applications are described in the following
sections.
Issue 2.01
5 Feb 1996
Page 1-3