Download E2000 Miniature Circuit Breakers

Transcript
EntelliGuard® G Circuit Breaker Application Guide
Section 3. EntelliGuard TU Trip Unit System
DET-653A
02 Apr 09
External Zero Sequence Input
The EntelliGuard TU trip unit is able to accept input from an
externally calculated Ground Fault current. The Ground Fault
current may be derived using a single Zero Sequence CT or
multiple phase CTs connected in a residual summation
scheme. External CE marked Zero Sequence or ground
return CTs are available for IEC applications, but are not UL
Listed. Phase CTs used for a summation connection are UL
Listed. Applications for this capability include sensing at the
ground return connection for a transformer or generator as
well as application in multiple source grounded systems.
Ground Fault Pickup Settings
All UL 489 and UL 1066 circuit breakers are limited to a
maximum nominal pickup setting of 1200A per the National
Electrical Code or 60% of the sensor size, whichever is lower.
The minimum setting is 20% of sensor size. The available
maximum settings per sensor may be seen in Table 3.8.
Ground Fault Protection Curves
The EntelliGuard TU trip unit offers four different shapes for
the ground fault function:
• Definite time with adjustable time delay.
2
• I t slope with adjustable time delay.
4
• I t slope (fuse shaped) with adjustable time delay.
2
• Selective double break I t with adjustable time delay.
The definite time and I2t characteristics provide the
traditional GF curve shapes. The I4t characteristic provides a
shape more in line with downstream fuses. GE’s unique
selective double break I2t characteristic provides the most
selective setting possible while still meeting the applicable
UL and NEC standards. In many cases, an 800A circuit
breaker may be used under a 1200A ground fault curve
selectively (Fig. 3.9).
Figure 3.9. Ground Fault Characteristics
1,000.00
Table 3.8. Ground Fault Time Delay Bands
Minimum
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
Maximum
0.60
0.60
0.60
0.60
0.60
0.60
0.48
0.40
0.37
0.30
0.24
0.20
Ground Fault Time Delay Bands
Ground Fault Time Delay Bands used in the EntelliGuard G
circuit breakers range from 42msec to 942msec. In Power
Break I, Power Break II, WavePro and AKR circuit breakers,
the minimum GF Time Delay Band is 58msec and the
maximum is 417msec.
The available minimum settings per circuit breaker type are
shown in Table 3.9. The maximum Time Delay Band setting
for all circuit breakers is 0.940sec with a 1sec clear.
Table 3.9. Minimum Ground Fault Pickup and Clear Time
Setting
Power Break I & II,
AKR & WavePro
EntelliGuard G
Minimum pickup
0.058sec
0.042sec
Minimum clear
0.113sec
0.097sec
Maximum pick
0.417sec
0.940sec
Maximum clear
0.470sec
1.000sec
® 2009 General Electric All Rights Reserved
1200A
NEC Maximum
100.00
SGF
10.00
Seconds
Sensor
400
600
800
1200
1600
2000
2500
3000
3200
4000
5000
6000
3000A, 1Sec.
NEC point
Point
1.00
I2t
I4t
0.10
0.01
1,000
10,000,,000
Amperes
10,000
10,000
100,000
100,000
Instantaneous Protection
The EntelliGuard TU trip unit may provide several types of
Instantaneous protection, depending on the circuit breaker
in which it is installed. The different types of Instantaneous
protection are as follows:
• Adjustable Selective Instantaneous: Provided on Power
Break II, WavePro, AKR and EntelliGuard G.
• Extended Range Adjustable Selective Instantaneous: An
available option on ANSI EntelliGuard G circuit breakers.
• High Set Instantaneous Overcurrent Trip: Provided on
Power Break II and some EntelliGuard G circuit breakers,
also called an override.
• Making Current Release (MCR): Provided on all EntelliGuard
G circuit breakers.
• Reduced Energy Let-Through Instantaneous Trip: An
available option on Power Break II, WavePro, AKR and
EntelliGuard G circuit breakers.
15