EntelliGuard® G Circuit Breaker Application Guide Section 3. EntelliGuard TU Trip Unit System DET-653A 02 Apr 09 External Zero Sequence Input The EntelliGuard TU trip unit is able to accept input from an externally calculated Ground Fault current. The Ground Fault current may be derived using a single Zero Sequence CT or multiple phase CTs connected in a residual summation scheme. External CE marked Zero Sequence or ground return CTs are available for IEC applications, but are not UL Listed. Phase CTs used for a summation connection are UL Listed. Applications for this capability include sensing at the ground return connection for a transformer or generator as well as application in multiple source grounded systems. Ground Fault Pickup Settings All UL 489 and UL 1066 circuit breakers are limited to a maximum nominal pickup setting of 1200A per the National Electrical Code or 60% of the sensor size, whichever is lower. The minimum setting is 20% of sensor size. The available maximum settings per sensor may be seen in Table 3.8. Ground Fault Protection Curves The EntelliGuard TU trip unit offers four different shapes for the ground fault function: • Definite time with adjustable time delay. 2 • I t slope with adjustable time delay. 4 • I t slope (fuse shaped) with adjustable time delay. 2 • Selective double break I t with adjustable time delay. The definite time and I2t characteristics provide the traditional GF curve shapes. The I4t characteristic provides a shape more in line with downstream fuses. GE’s unique selective double break I2t characteristic provides the most selective setting possible while still meeting the applicable UL and NEC standards. In many cases, an 800A circuit breaker may be used under a 1200A ground fault curve selectively (Fig. 3.9). Figure 3.9. Ground Fault Characteristics 1,000.00 Table 3.8. Ground Fault Time Delay Bands Minimum 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 Maximum 0.60 0.60 0.60 0.60 0.60 0.60 0.48 0.40 0.37 0.30 0.24 0.20 Ground Fault Time Delay Bands Ground Fault Time Delay Bands used in the EntelliGuard G circuit breakers range from 42msec to 942msec. In Power Break I, Power Break II, WavePro and AKR circuit breakers, the minimum GF Time Delay Band is 58msec and the maximum is 417msec. The available minimum settings per circuit breaker type are shown in Table 3.9. The maximum Time Delay Band setting for all circuit breakers is 0.940sec with a 1sec clear. Table 3.9. Minimum Ground Fault Pickup and Clear Time Setting Power Break I & II, AKR & WavePro EntelliGuard G Minimum pickup 0.058sec 0.042sec Minimum clear 0.113sec 0.097sec Maximum pick 0.417sec 0.940sec Maximum clear 0.470sec 1.000sec ® 2009 General Electric All Rights Reserved 1200A NEC Maximum 100.00 SGF 10.00 Seconds Sensor 400 600 800 1200 1600 2000 2500 3000 3200 4000 5000 6000 3000A, 1Sec. NEC point Point 1.00 I2t I4t 0.10 0.01 1,000 10,000,,000 Amperes 10,000 10,000 100,000 100,000 Instantaneous Protection The EntelliGuard TU trip unit may provide several types of Instantaneous protection, depending on the circuit breaker in which it is installed. The different types of Instantaneous protection are as follows: • Adjustable Selective Instantaneous: Provided on Power Break II, WavePro, AKR and EntelliGuard G. • Extended Range Adjustable Selective Instantaneous: An available option on ANSI EntelliGuard G circuit breakers. • High Set Instantaneous Overcurrent Trip: Provided on Power Break II and some EntelliGuard G circuit breakers, also called an override. • Making Current Release (MCR): Provided on all EntelliGuard G circuit breakers. • Reduced Energy Let-Through Instantaneous Trip: An available option on Power Break II, WavePro, AKR and EntelliGuard G circuit breakers. 15